OWB Monitor - Firmware Config

The OWB monitor runs thesada-fw on a LILYGO T-SIM7080-S3. This page covers the OWB-specific configuration.

Hardware

Component Details
Board LILYGO T-SIM7080-S3 (ESP32-S3 + SIM7080G + AXP2101)
Temperature 4x DS18B20 on GPIO12 (1-Wire bus)
Current ADS1115 with 2x SCT-013-030 CT clamps (I2C SDA=1, SCL=2)
Battery 18650 LiPo via AXP2101, solar input
Connectivity WiFi primary, LTE-M cellular fallback

config.json

The full config lives on LittleFS at /config.json. Edit via the web UI, HTTP API, or MQTT CLI.

Key sections for OWB

WiFi + MQTT:

"wifi": {
  "networks": [
    { "ssid": "YourIOT", "password": "your-password" }
  ],
  "ap_password": "at-least-8-chars",
  "ap_timeout_s": 300
},
"mqtt": {
  "broker": "mqtt.example.com",
  "port": 8883,
  "user": "mqtt",
  "password": "your-mqtt-password",
  "topic_prefix": "thesada/owb",
  "ha_discovery": true,
  "buffer_in": 4096,
  "buffer_out": 4096
}

ap_password has to be at least 8 characters and must not be changeme. The fallback AP does not start otherwise. web.password has the same rejection.

Temperature sensors (DS18B20):

"temperature": {
  "enabled": true,
  "pin": 12,
  "interval_s": 60,
  "auto_discover": true,
  "conversion_wait_ms": 850,
  "read_retries": 2,
  "max_delta_c": 40,
  "unit": "F",
  "sensors": [
    { "address": "28...", "name": "House Supply" },
    { "address": "28...", "name": "House Return" },
    { "address": "28...", "name": "Barn Supply" },
    { "address": "28...", "name": "Barn Return" }
  ]
}
  • Set auto_discover: true on first boot to detect sensor addresses automatically
  • After discovery, sensor addresses and names are saved to config
  • conversion_wait_ms: 850 gives reliable reads on long wire runs (default 750)
  • unit: "F" publishes in Fahrenheit (thresholds in alert scripts always use Celsius)
  • read_retries: 2 re-reads a probe on a transient bus fault before reporting it stale (default 2). DS18B20 scratchpad CRC is always checked by the driver; this adds retries on top.
  • max_delta_c: 40 holds a reading that jumps more than 40 C from the last accepted one - guards against marginal-bus garbage (long flying leads can read wildly wrong but CRC-valid). The held probe publishes as stale with no value. The next reading within 40 C of the held one is accepted and becomes the new baseline, so one real step (a probe returning mid fire-up) does not lock it out. The first reading after boot is accepted unchecked. Set 0 to disable.
  • 85.0 C is the DS18B20 power-on value, read after a reset before the first conversion. A reading of exactly 85.0 C is held back and the probe publishes as stale, logged as temp.read_rejected reason=power_on, unless the last accepted reading is within 2 C of it. This check runs even with max_delta_c: 0 and on the first reading after boot. Repeats never confirm 85.0, and it never counts as the reading that confirms a jump. A boiler that really sits at 85 C keeps reading, because its last reading was close. One already at 85 C at boot reads stale until its first reading that is not exactly 85.00.

Multiple 1-Wire buses: to drive more than one bus, replace the scalar pin with a buses list. Each bus gets its own GPIO; probes from all buses aggregate into one sensor list (DS18B20 ROM addresses are globally unique):

"temperature": {
  "enabled": true,
  "buses": [ { "pin": 9 }, { "pin": 10 } ],
  "auto_discover": true
}

The scalar pin form still works and is treated as a single bus.

Live probe management: attach or swap a probe without rebooting - run temp.discover over the CLI to re-walk every bus and pick up new probes; temp.discover --prune drops probes that no longer respond and clears their stale entries.

Current sensing (ADS1115 + CT clamps):

"ads1115": {
  "enabled": true,
  "i2c_sda": 1,
  "i2c_scl": 2,
  "address": 72,
  "interval_s": 60,
  "line_voltage": 120,
  "channels": [
    { "name": "House Pump", "mux": "A0_A1", "gain": 0.256, "clamp_a_per_v": 30 },
    { "name": "Barn Pump", "mux": "A2_A3", "gain": 0.256, "clamp_a_per_v": 30 }
  ]
}
  • line_voltage: 120 - used for power (watts) calculation. Update if your supply voltage differs.
  • clamp_a_per_v: 30 - CT clamp ratio, amps per 1 V of output. SCT-013-030 = 30, SCT-013-005 = 5. Defaults to 30 if omitted.
  • RMS sampling: 30 samples over 2x 60Hz cycles for accurate AC current measurement
  • "dc": true on a channel reads the mean of the samples instead of the AC RMS, for a DC sensor such as a pressure transducer. The value is still scaled by clamp_a_per_v and published as current, so set that to the sensor’s units per volt. The boot log shows coupling=dc. Default false, an AC current clamp.
  • dc does not change gain. Pick a gain for a DC channel from the sensor’s highest output, not from the clamp examples above: 0.256 suits a CT clamp’s small swing and pins a 0.5 to 4.5 V transducer at the top of the range. gain is the full-scale voltage in V, rounded up to the next ADS1115 range: 0.256, 0.512, 1.024, 2.048, 4.096 or 6.144. A rounded value logs ads.gain_rounded, and an absent gain means 1.024. Choose the smallest range at or above the sensor’s maximum: a sensor that tops out at 4.5 V needs 6.144, one that tops out at 3 V needs 4.096. A DC channel has no saturation check, so a signal past full scale reads as full scale with no log line.
  • The range sets the scale, not what the input pins tolerate. Per the ADS1115 datasheet every analog input has to stay between GND and the chip’s supply (VDD), whatever the gain. On a chip powered from 3.3 V nothing above 3.3 V can be read, even at 6.144. A 5 V sensor on a chip powered from 3.3 V needs a divider, and the clamp_a_per_v scale then has to include the divider ratio.

Multiple ADS1115 chips: to read more than 4 channels, wire a second ADS1115 at a different I2C address (ADDR pin to VDD = 0x49) and list both under devices. Each device carries its own channels; i2c_sda / i2c_scl / interval_s / line_voltage stay shared at the top level:

"ads1115": {
  "enabled": true,
  "i2c_sda": 1,
  "i2c_scl": 2,
  "interval_s": 60,
  "line_voltage": 120,
  "devices": [
    { "address": 72, "channels": [ { "name": "House Pump", "mux": "A0_A1", "gain": 0.256 } ] },
    { "address": 73, "channels": [ { "name": "Barn Pump",  "mux": "A0_A1", "gain": 0.256 } ] }
  ]
}

The scalar address + top-level channels form still works and is treated as a single device.

Telegram alerts:

"telegram": {
  "enabled": true,
  "bot_token": "your-bot-token",
  "chat_ids": ["your-chat-id"]
}

Alert logic is in /scripts/rules.lua on LittleFS (hot-reloadable, no recompile needed).

Deployment

First flash (USB):

cp examples/config.json.example data/config.json
# edit config.json with your WiFi, MQTT, sensor names
pio run -e esp32-owb --target upload
pio run -e esp32-owb --target uploadfs

Subsequent updates (OTA):

The node checks GitHub releases every 6 hours and auto-updates. Or trigger manually:

# Via MQTT CLI
mosquitto_pub ... -t 'thesada/owb/cli/ota.check' -m ''

# Via HTTP (if on same network)
curl -u admin:your-password -X POST http://<node-ip>/ota -F 'firmware=@build/firmware.bin'

Push scripts remotely:

printf '/scripts/rules.lua\n' > /tmp/payload.bin
cat rules.lua                >> /tmp/payload.bin
mosquitto_pub ... -t 'thesada/owb/cli/fs.write' -f /tmp/payload.bin
mosquitto_pub ... -t 'thesada/owb/cli/lua.reload' -m ''

MQTT topics

All sensor data publishes to per-sensor topics under the configured prefix:

Topic Value
thesada/owb/sensor/temperature/house_supply 65.20
thesada/owb/sensor/temperature/house_return 57.10
thesada/owb/sensor/current/house_pump 0.70
thesada/owb/sensor/power/house_pump 84.0
thesada/owb/sensor/battery/percent 100
thesada/owb/status online / offline (LWT)
thesada/owb/alert alert messages from rules.lua

Home Assistant picks these up automatically via MQTT auto-discovery (when ha_discovery: true).

Verification

After deployment, verify with the MQTT CLI:

mosquitto_pub ... -t 'thesada/owb/cli/version' -m ''
mosquitto_pub ... -t 'thesada/owb/cli/sensors' -m ''
mosquitto_pub ... -t 'thesada/owb/cli/selftest' -m ''

Or via the web dashboard at http://<node-ip>/. The sensor page is public. Admin login rejects changeme, an empty password, and a missing one.